The CO2 level is an indicator worth watching closely. The concentration of certain gases in the air we breathe deserves attention, for very different reasons. Carbon monoxide (CO), carbon dioxide (CO2), and various volatile organic compounds (VOCs) each have very different effects.
Let's focus here on the case of CO2, or "carbonic gas".
Impact on global warming
It's hard to skip over this topic, even though it isn't the main focus of what we want to cover here.
Contrary to popular belief, carbon dioxide is present in only very small amounts in the Earth's atmosphere (in its current state). It accounts for around 0.04%, far behind nitrogen (78%), oxygen (21%) and argon (1%).
The effect of its increase in the open atmosphere isn't to stop us breathing. It's rather to alter the average temperature, and therefore the climate, through the greenhouse effect, which limits the Earth's capacity to radiate heat away.
A chain of phenomena, essentially linked to human activity, can be cited: deforestation and wildfires, energy production from fossil fuels, and so on.
For more than a century now, these have driven a rapid rise in CO2 levels. The annual average CO2 level has already passed 400 ppm (parts per million, by volume), growing by 2 ppm a year.
CO2, a good indicator of poor ventilation
Generally speaking, good ventilation lowers the risk of respiratory illness. What's more, a CO2 concentration above 1,000 ppm causes a (reversible) reduction in cognitive performance.
As a result, in a Covid-19 context, indoor air quality becomes essential. Sars-Cov-2 can spread via aerosols - tiny droplets released when breathing and speaking. These aerosols travel over distances of more than 2m. A simple, effective way to reduce aerosol contamination is to ventilate premises effectively.
Indeed, in an enclosed space, CO2 is largely produced by human breathing. And the amount of CO2 in the air indicates how well-ventilated a space is. The higher the CO2 level, the less ventilated the room, and the greater the potential viral load produced by its occupants.
Outdoors, CO2 concentration sits between 350 and 450 ppm. Taking an average of 400 ppm, the link between a room's air quality and its CO2 concentration is set out in the following values (per EN 16798-1, the building ventilation standard published in 2019):
- Below 950 ppm: excellent air quality;
- Between 950 and 1,200 ppm: average air quality;
- Between 1,200 and 1,750 ppm: moderate air quality;
- Above 1,750 ppm: poor air quality.
Even stricter thresholds during the Covid crisis
In an enclosed space, it's not uncommon to exceed the first threshold within a few minutes - for example in venues open to the public, meeting rooms or poorly ventilated classrooms.
That's why, during the Sars-Cov-2 pandemic, thresholds were tightened further. In its opinion of 28 April 2021, France's High Council for Public Health recommended an even lower threshold: "A CO2 concentration above a threshold of 800 ppm should, in all cases, lead to the room not being occupied, and to action being taken in terms of ventilation/air renewal and/or reducing the number of people admitted into premises open to the public."
How does a CO2 detector work?
The main technique used is a non-dispersive infrared sensor (also known as an NDIR sensor).
The detector compares the infrared beam absorption from its emitter (tuned to a carefully chosen wavelength, typically 4.26 micrometres for CO2) between the ambient air and a reference - for example a capsule containing the target gas (or a factory-set value). After filtering and processing, the concentration is derived.
CO2 variation in an enclosed space
A picture is worth a thousand words... below is an example of CO2 concentration variation (measured via the Agora Software solution) in a meeting room on Monday 13 and Tuesday 14 December (so, in winter). There are around 20 people in the room, with readings taken every 30 minutes.
The "empty room" level (400 ppm) is reached overnight from Sunday 12 to Monday 13, after which the curve tracks attendance fairly closely, with a clear lunch-break dip and a fairly slow decline overnight (likely due to a lack of ventilation). As for the peak values (3,300 ppm), they're far too high against the recommendations.
Measuring is good, acting is (much) better
Once the sensor is installed, the question becomes how to use the information. One initial approach is to store it in a database (a "lake"), then generate periodic reports summarising how the measured values have evolved.
These reports help identify rooms with recurring issues and, in some cases, plan ventilation improvement works.
Two problems remain: someone has to be responsible for reviewing the reports on a regular basis, and immediate situations go untreated, leaving people exposed to poor ventilation in the meantime.
It is, however, possible to act quickly whenever critical zones are crossed, by notifying people able to act locally, or even by directly controlling a ventilation system where the room has one.
A simple example applied to a school would be to alert the facilities manager once a first threshold is crossed, then the teacher in charge of the class as soon as the level requires it, simply asking them to open the window.
And if they haven't confirmed the action after a few minutes, ask the facilities manager to carry it out themselves.
Acting quickly without breaking the bank: it's possible
The effects of excess carbon dioxide concentration in the atmosphere are more than problematic. That said, its bad reputation shouldn't stop us from using it - much like the canary in a coal mine - as a good indicator of poor ventilation: quick to set up, reliable and inexpensive. As long as you're listening...